62 Commercial Cooling Statistics on Equipment, Energy, and Efficiency

Commercial cooling spans packaged equipment, chillers, heat pumps, district systems, and other technologies serving U.S. commercial buildings. The statistics below cover 2018 survey estimates, 2019–2050 forecasts, global cooling scenarios, and selected chiller case studies with explicit populations, periods, and limitations.

Key Commercial Cooling Statistics

The most broadly useful commercial cooling figures include:

  • In 2018, 2,565 thousand U.S. commercial buildings reported packaged air-conditioning units.
  • In 2018, 1,309 thousand U.S. commercial buildings reported residential-type central air conditioners.
  • In 2018, 735 thousand U.S. commercial buildings reported individual air conditioners.
  • In 2018, 202 thousand U.S. commercial buildings reported central chillers.
  • In 2018, 492 thousand U.S. commercial buildings reported heat pumps as cooling equipment.
  • In 2018, 55 thousand U.S. commercial buildings reported district chilled water.
  • In 2018, packaged units served 55% of U.S. commercial buildings with cooling.
  • In 2018, packaged units served 66% of air-conditioned buildings in hot or very hot U.S. climate zones.
  • In 2018, packaged-unit buildings covered 56,416 million square feet of U.S. commercial floorspace.
  • In 2018, commercial buildings with central chillers averaged 88.8 thousand square feet per building.
  • In 2018, cooling energy intensity was 14.2 thousand Btu per square foot in hot or very hot U.S. climates.
  • In 2018, cooling energy intensity was 2.3 thousand Btu per square foot in cold or very cold U.S. climates.
  • In 2018, major fuels used for U.S. commercial cooling totaled 589 trillion Btu.
  • In 2018, electricity supplied 98% of major-fuel cooling energy in U.S. commercial buildings.
  • In 2018, 31% of U.S. commercial buildings were all-electric, representing 1.8 million buildings.
  • From 2019 to 2050, U.S. commercial-building floorspace was projected to expand 34%.
  • From 2019 to 2050, warehouse floorspace was projected to expand 43% in the United States.
  • From 2019 to 2050, warehouse air-conditioning energy consumption was projected to increase 15%.
  • Across three U.S. Navy case-study sites from 2005–2007, magnetic-bearing chiller compressor power savings averaged 49%.
  • In a 2005–2007 Newport, Rhode Island Navy project, an 80-ton new-chiller installation saved 227,760 kWh annually and 65% of power.

Contents

Commercial Cooling Equipment Adoption and Building Coverage

The 2018 Commercial Buildings Energy Consumption Survey (CBECS) provides a nationally representative view of U.S. commercial buildings. Its equipment responses allow more than one equipment type per building, so the categories below are overlapping reported populations rather than a single market-share total. 2018 Commercial Buildings Energy Consumption Survey: Table B1, Summary table

Cooling equipment reported U.S. commercial buildings, 2018 Measurement note
Packaged air-conditioning units 2,565 thousand Estimate; categories can overlap
Residential-type central air conditioners 1,309 thousand Estimate; categories can overlap
Individual air conditioners 735 thousand Estimate; categories can overlap
Heat pumps used as cooling equipment 492 thousand Estimate; categories can overlap
Central chillers 202 thousand Estimate; categories can overlap
Swamp coolers 85 thousand Estimate; categories can overlap
District chilled water 55 thousand Estimate; categories can overlap

Packaged units were used by 55% of U.S. commercial buildings with cooling in 2018. In hot or very hot climate zones, the share was 66% of air-conditioned buildings, compared with 48% in cold or very cold climate zones; EIA classifies these climate zones using ASHRAE Standard 169-2021. Cooling commercial buildings is six times more energy-intensive in hot climates than cold

Commercial Cooling Data by System Type, Floorspace, and Operating Hours

System presence describes only part of commercial cooling’s scale. The 2018 CBECS estimates also show the floorspace, workers, average building size, and weekly operating hours associated with buildings reporting each equipment category.

System category Floorspace, million sq. ft. Workers, thousand Mean building size, thousand sq. ft. Hours per week
Packaged air-conditioning units 56,416 53,368 22.0 66
Residential-type central air conditioners 18,437 16,384 14.1 58
Individual air conditioners 13,767 10,038 18.7 69
Central chillers 17,910 21,736 88.8 75
Heat pumps 11,138 11,637 22.6 65
District chilled water 4,288 Not reported in supplied measure Not reported in supplied measure 73

The packaged-unit category covered 56,416 million square feet and represented 53,368 thousand workers. Buildings reporting central chillers were much larger on average, at 88.8 thousand square feet, and operated an average of 75 hours per week, while individual-air-conditioner buildings averaged 69 hours. 2018 Commercial Buildings Energy Consumption Survey: Table B1, Summary table

Because CBECS equipment categories may overlap, floorspace and worker figures should not be added across rows to produce a national total. The estimates describe buildings reporting each equipment type, not mutually exclusive technology segments.

Commercial Cooling Energy Use Across U.S. Climate Zones

Climate affects both the intensity of cooling energy use and the share of a building that receives cooling. In 2018, cooling energy intensity was 14.2 thousand Btu per square foot in hot or very hot U.S. climates, versus 2.3 thousand Btu per square foot in cold or very cold climates.

U.S. climate grouping Cooling energy intensity, 2018 Buildings cooling all floorspace, 2018 Packaged units among air-conditioned buildings
Hot or very hot 14.2 thousand Btu/sq. ft. 52% 66%
Cold or very cold 2.3 thousand Btu/sq. ft. 25% 48%

EIA calculated the intensity measure from major-fuel cooling consumption divided by floorspace using those fuels. It is a modeled or calibrated end-use estimate, not a direct submeter reading, and the climate-zone comparison follows the supplied ASHRAE-based classification. Cooling commercial buildings is six times more energy-intensive in hot climates than cold

The same source reports that 52% of buildings in hot or very hot climates cooled all floorspace in 2018, compared with 25% in cold or very cold climates. These are survey estimates for the share of buildings, not the share of total floorspace.

Commercial Cooling Electricity, Fuels, District Cooling, and All-Electric Buildings

Major fuels used for U.S. commercial cooling totaled 589 trillion Btu in 2018. The measure includes electricity, natural gas, district heat, and fuel oil covered by CBECS end-use estimates.

Electricity supplied 98% of that major-fuel cooling energy. This percentage applies to the 589 trillion Btu total and should not be read as a separate estimate of every cooling-related energy flow outside the covered CBECS end uses. Cooling commercial buildings is six times more energy-intensive in hot climates than cold

District chilled water was reported in about 55 thousand commercial buildings with cooling, or about 1% of U.S. commercial buildings with cooling, in 2018. The rounded share and building count describe the district-chilled-water population rather than all buildings using centralized cooling. Cooling commercial buildings is six times more energy-intensive in hot climates than cold

All-electric buildings accounted for 31% of U.S. commercial buildings, or 1.8 million buildings, in 2018. EIA’s definition means that only electricity is used for end uses electricity can perform; on-site generation may use other sources, so this is not a claim that every energy input at every site was electricity. 2018 CBECS data related to all-electric buildings

Forecasts describe scenarios, not observed outcomes. EIA’s AEO2020 Reference case projected total U.S. commercial-building floorspace to expand 34% from 2019 to 2050, creating a larger physical base for future cooling demand. EIA projects air-conditioning energy use to grow faster than any other use in buildings

The AEO2020 Reference case also projected the following commercial-building changes:

  • Office buildings were projected to account for 25% of U.S. commercial-sector air-conditioning energy in 2050.
  • Warehouse floorspace was projected to expand 43% from 2019 to 2050.
  • Warehouse air-conditioning energy consumption was projected to increase 15% over the same period.

The warehouse figures are not a simple one-for-one relationship between floorspace and cooling energy: the supplied EIA limitation notes that cooling intensity varies by building type. The projections should therefore be treated as scenario outputs rather than guaranteed adoption or consumption results.

The IEA’s global figures cover a broader population than U.S. commercial buildings. Its 2018 report baseline estimated that air conditioners and electric fans accounted for about 20% of electricity used in buildings worldwide, while its scenario projected that around two-thirds of the world’s households could have an air conditioner by 2050. The Future of Cooling: Opportunities for energy-efficient air conditioning

That IEA scenario also projected China, India, and Indonesia to account for half of the global air-conditioner stock by 2050. These household and global-building measures should not be substituted for commercial-building adoption rates.

Commercial Chiller Efficiency, Controls, Costs, and Measured Savings

Chiller efficiency evidence in the supplied sources consists of engineering guidance and site-specific case studies, not representative market averages. Three U.S. Navy facilities reported average magnetic-bearing chiller compressor power savings of 49% across 2005–2007, but the result depends on each site and load profile. Magnetic-Bearing Chiller Compressors

Case-study site and project Capacity Annual savings Power savings Cost or payback
San Diego, California retrofit 240 tons 176,717 kWh 40% $178,787; 8.4-year payback
Newport, Rhode Island new chiller 80 tons 227,760 kWh 65% $100,783; 3.8-year payback
Jacksonville, Florida compressor retrofit 120 tons 284,407 kWh 41% Not supplied

These Navy results are individual demonstrations from 2005–2007. Their reported tariffs, project assumptions, site conditions, and load profiles mean that the costs and paybacks are not typical commercial cooling prices. Magnetic-Bearing Chiller Compressors

DOE guidance from 2011 estimated that chilled-water reset savings could reach 0.5%–0.75% per degree Fahrenheit with fixed-speed drives and 2.0%–3.0% per degree Fahrenheit with variable-speed drives. Condenser-water reset savings were estimated at 0.75%–1.25% per degree Fahrenheit with fixed-speed drives and 1.5%–2.0% per degree Fahrenheit with variable-speed drives.

The same guidance estimated that variable-speed drives could reduce cooling-delivery-system energy use by 30%–50%, depending on load profile. These are technology guidance ranges rather than universal measured outcomes. Hospitals Benefit by Improving Inefficient Chiller Systems

A Memorial Sloan-Kettering Cancer Center case study in New York projected $486,500 in annual energy-cost savings over baseline during 2006–2009. The implementation received a $598,000 NYSERDA grant in 2008–2009; both figures are project-specific, and neither is a sector-wide commercial cooling average. Hospitals Benefit by Improving Inefficient Chiller Systems